Belden 8760 data sheet

Loading...

8760 Multi-Conductor - Shielded Twisted Pair Cable Description 18 AWG stranded (16x30) tinned copper conductors, polyethylene insulation, twisted pair, overall Beldfoil® shield (100% coverage), 20 AWG stranded tinned copper drain wire, PVC jacket. Put Ups and Colours Item # 8760 0601000 8760 06010000 8760 0602000 8760 060250 8760 060500 8760 0605000 8760 060U1000 8760 060U500

Putup 1,000 FT 10,000 FT 2,000 FT 250 FT 500 FT 5000 FT 1,000 FT 500 FT

Ship Weight 26.000 LB 280.000 LB 56.000 LB 7.250 LB 14.500 LB 150.000 LB 28.000 LB 14.500 LB

Jacket Colour CHROME CHROME CHROME CHROME CHROME CHROME CHROME CHROME

Notes C CY C

2 2 2 2 2 2 2 2

C C

Item Description #18 LDPE SH PVC CHR #18 LDPE SH PVC CHR #18 LDPE SH PVC CHR #18 LDPE SH PVC CHR #18 LDPE SH PVC CHR #18 LDPE SH PVC CHR #18 LDPE SH PVC CHR #18 LDPE SH PVC CHR

Notes: C = Create Reel Put-up Y = Final put-up length may vary -10% to +20% from length shown may contain 2 pieces, minimum length of any one piece is 1500’.

Physical Characteristics (overall) Conductor – AWG # Pairs 1.000

AWG 18

Stranding 16x30

Conductor Material TC – Tinned Copper

Insulation – Insulation Material Ins Material PE – Polyethylene

Wall Thickness (in.) 0.019

Outer Shield - Outer Shield Material Outer Shield Trade Name Beldfoil®

Type Tape

Outer Shield Material Aluminium Foil-Polyester Tape w/Shorting Fold

% Coverage (%) 100

Outer Shield Drain Wire AWG AWG 20

Stranding 7x28

Drain Wire Conductor Material TC – Tinned Copper

Outer Jacket – Outer Jacket Material Outer Jacket Material PVC – Polyvinylchloride

Nom. Wall Thickness (in.) 0.028

Overall Cabling – Overall Nominal Diameter: 0.222 in. Pair Colour Code Chart Number 1

Colour Black & Clear

Pair Lay Length & Direction Lay Length (In.) 2.500

Twists/ft. (twist/ft) 4.800

Mechanical Characteristics (overall) Operating Temperature Range UL Temperature Range Bulk Cable Weight Max. Recommended Pulling Tension Min. Bend Radius (Install)/Minor Axis

-20oC to +60oC 60 oC (UL AWM Style 2092) 26.6 00 lbs/1000ft 62 lbs 2.250 In.

Applicable Specifications and Agency Compliance (overall) Application NEC (UL) Specification CEC/C (UL) Specification AWM Specification EU CE Mark EU RoHS Compliant (commence date: dd/mm/yyyy) Flame Test UL Flame Test Plenum/Non-Plenum Plenum Plenum Number

CM CM UL Style 2092 (300 V 60°C)

(01/04/2005)

UL 1685 UL Loading

88760, 87760 & 82760

Electrical Characteristics (overall) Nom. Characteristics Impedance Impedance (Ohm) 57 .000

Nom. Inductance Inductance (µH/ft) 0.180

Nom. Capacitance Conductor to Conductor Capacitance (pF/ft) 29.800

Nom. Capacitance Conductor to Other Conductor & Shield Capacitance (pF/ft) 44 .000

Nominal Conductor DC Resistance DCR @ 20oC (Ohm/1000 ft) 6.500

Max. Operating Voltage – UL Voltage 300 V RMS (UL AWM Style 2092)

Max. Recommended Current Current 5.2 Amps per conductor @ 25oC

Contact Cables Ltd , Unit 3 Brook Road, Bicton Industrial Estate, Kimbolton,Cambs,PE28 0EY Telephone: 01480 861348 Fax: 01480 861560 www.contactcables.com

Loading...

Belden 8760 data sheet

8760 Multi-Conductor - Shielded Twisted Pair Cable Description 18 AWG stranded (16x30) tinned copper conductors, polyethylene insulation, twisted pair...

111KB Sizes 6 Downloads 0 Views

Recommend Documents

8760 Technical Data Sheet (Metric) - Belden eDesk
Jan 1, 2004 - 18 AWG stranded (16x30) tinned copper conductors, polyethylene insulation, twisted pair, overall BeldfoilÂ

8760 Technical Data Sheet - Belden Global Catalog
Jan 1, 2004 - Part Number: 8760. Audio/Control/Instrumentation, (1 pr) 18 AWG (16x30) TC, PO/PVC, Foil Shld,. CM. Produc

3076F Technical Data Sheet - Belden
Jan 1, 2004 - CEC/C(UL) Specification: CMG. EU Directive 2000/53/EC (ELV):. Yes. EU Directive 2003/96/EC (BFR):. Yes. EU

8760 Technical Data Sheet (English)
... 2000/53/EC (ELV):. Yes. EU Directive 2002/95/EC (RoHS):. Yes. EU RoHS Compliance Date (mm/dd/yyyy):. 01/01/2004. EU

1694A Technical Data Sheet - Belden Global Catalog
Jan 1, 2004 - 2017 Belden, Inc. All Rights Reserved. Although Belden makes every reasonable effort to ensure their accur

9730 Technical Data Sheet (Metric) - Belden eDesk
Jan 1, 2004 - 24 AWG stranded (7x32) tinned copper conductors, Datalene® insulation, twisted pairs, individually shield

3105A Technical Data Sheet - Belden Global Catalog
Oct 1, 2005 - CEC/C(UL) Specification: CM. EU Directive 2000/53/EC (ELV):. Yes. EU Directive 2002/96/EC (WEEE):. Yes. EU

8723 Technical Data Sheet - Belden Global Catalog
Jan 1, 2004 - CEC/C(UL) Specification: CM. EU Directive 2000/53/EC (ELV):. Yes. EU Directive 2003/96/EC (BFR):. Yes. EU

8760 Technical Data Sheet (English) - Farnell
Sep 2, 2017 - 18 AWG stranded (16x30) tinned copper conductors, polyethylene insulation, twisted pair, overall BeldfoilÂ

Belden 8760 0601000 | Interstate Wire
18 AWG Stranded (16x30) TC Conductors ~ Twisted Pair ~ Overall Beldfoil Shield (100% Coverage) ~ 20 AWG Stranded TC Drai

Drama (2018) DVDRip Malayalam Movie Watch Online Free | Planta de acuario.lemna minor (planta flotante)lenteja de agua. Porción 10x10 | Swedish Krona